{{ 'fb_in_app_browser_popup.desc' | translate }} {{ 'fb_in_app_browser_popup.copy_link' | translate }}
{{ 'in_app_browser_popup.desc' | translate }}
Free shipping on HK orders over $2000
Welcome!
Kanomax Duct Air Leakage Tester – Model 6905
Made in Japan
Model: DALT 6905
Not enough stock.
Your item was not added to your cart.
Not enough stock.
Please adjust your quantity.
{{'products.quick_cart.out_of_number_hint'| translate}}
{{'product.preorder_limit.hint'| translate}}
Limit {{ product.max_order_quantity }} per order.
Only {{ quantityOfStock }} item(s) left.
Overview
The Kanomax Duct Air Leakage Tester – Model 6905 sets a new benchmark for commercial duct system testing. Lighter, more compact, and more powerful than its predecessor, it combines advanced engineering with user‑friendly features to deliver unmatched accuracy, portability, and compliance for HVAC professionals.
Key Features
● Compact, jobsite‑ready design with pneumatic tires and stair‑walker dolly
● Automated step‑by‑step test configuration compliant with SMACNA and AABC standards
● Dual testing capability: positive and negative (decay) pressure tests
● Certified accuracy: ±2.5% of reading, supports up to ±10 in.wg pressure
● Full‑color HD touch screen with intuitive interface and unit switching (°F/°C, CFM, m³/s, l/s, m³/h)
● No orifice plates required – simplified setup and execution
● Internal data storage with USB export for seamless reporting
● Ships with calibration certificate; annual NIST‑traceable calibration services available
● Optional heavy‑duty protective cover for enhanced durability
Applications
● HVAC duct leakage testing for energy efficiency and system integrity
● Commissioning and compliance verification for commercial duct systems
● On‑site testing in space‑constrained environments (fits through 21″ × 20″ roof hatches)
Accessories (Included)
● Integrated pneumatic tires and stair‑walker dolly
● Calibration certificate
● USB data export capability
● Medical evaluation software (integrated)
Technical Specs
| Specification | Value |
|---|---|
| Airflow Range (Large) | 41 – 483 CFM (70 – 821 m³/h) |
| Airflow Range (Small) | 2.4 – 21 CFM (4 – 36 m³/h) |
| Accuracy (Airflow) | ±2.5% of reading ± 0.1 m³/h |
| Resolution (Airflow) | 0.01 m³/h |
| Pressure Range | ±10 in.wg (±2500 Pa) duct static pressure |
| Accuracy (Pressure) | ±1% of reading ± 1 Pa |
| Resolution (Pressure) | 0.1 Pa |
| Temperature Range | 32 – 140 °F (0 – 60 °C) |
| Accuracy (Temp) | ±1 °F |
| Resolution (Temp) | 0.1 °F |
| Atmospheric Pressure | 20.6 – 38.3 in.Hg (70 – 130 kPa) |
| Accuracy (Atm. Press.) | ±2% of reading |
| Resolution | 0.1 kPa |
| Power Supply | DALT 6905‑0E: 110–120V, 1 Phase, 50/60Hz, 16A; DALT 6905‑1E: 220–240V, 1 Phase, 50/60Hz, 10A |
| Dimensions | 18.9W × 24.7D × 44.3H in (48 × 63 × 113 cm) |
| Weight | Approx. 60 kg (132 lbs) |
| Data Logging | Up to 1000 measurements |
Standards Compliance
● SMACNA HVAC (USA)
● BS EN 12237:2003 (EU)
● BS EN 1507:2006 (EU)
● DW/143 (EU)
● Eurovent 2/2 (EU)
● GB50243 (China)